Inspection Status: Completed

Inspection History: COT - FCOD - Fire Re-inspection

Date Description Inspector Results Comments
09/26/2013 COT - FCOD - Fire Re-inspection Completed All violations have been fixed except:

1. Sprinkler system to be removed - gave appeal to remove rather than maintain old kitchen sprinkler system. Not required...has UL 300 compliant hood/ansul system.

2. Posting of occupant load - I determined using factors for fixed seating without armrests and unconcentrated table/chairs factors. Max is 168.