Parcel: 117200250


Addresses:

265 S CHURCH AV


Inspection Status: Completed

Inspection History: COT - Fire - Complaint

Case Number - _1C5C7D2E27F46

Inspection Description - COT - Fire - Complaint

Inspection Status - Completed

Date Description Inspector Results Comments
10/25/2019 COT - Fire - Complaint Completed MOCA- FIREWATCH 10.25.19
02/25/2020 COT - Fire - Complaint Completed Systems due

Cleared by Kazal IROL .02.25.20
10/25/2019 COT - Fire - Complaint Completed MOCA FALL FUNDRAISER SE 10.25.19


Extings and Sprinklers just out of date, fire watch required.
04/24/2017 COT - Fire - Complaint Completed At event found sprinkler system past due. Unable to verify date of alrm insp.
Met w/ Tony (maintenance) , Gave order to have both systems tested asap.
09/30/2016 COT - Fire - Complaint Completed After hours found excessive combustible materials inside at special event. Requiring fire watch. Staff to perform FW. Log to be kept.
09/30/2016 COT - Fire - Complaint Completed Staff to do FW thru event.