Inspection History: COT - SIGN - Sign Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/22/2025 | COT - SIGN - Sign Final | Not Ready | 7/22/25 The Breaker Panel the dedicated circuit installed in is not safe. The face plate inside is missing. The timer needs to be only for the sign and be set to turn off at midnight per plan. The timer needs to be installed correctly and be specified for out door use. The timer currently installed is designed for indoor installation. Sign Final needs Electrical To pass Property Manager will address this and coordinate with sign company to reschedule inspections. |