Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - ENGR - Signage Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2026 | COT - ENGR - Signage Final | Not Ready | Sign electrical issues need corrected: Wall sign is set to run all night, needs to turn off at midnight per Tucson's outdoor lighting code. Verification of photocell, or other means, that dims the LED board to 200 nits or less after sunset is needed. LED board is switching images every 8 seconds, Tucson requires 60 seconds minimum between image changes. |
|