Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - ENGR - Sign Electrical
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2026 | COT - ENGR - Sign Electrical | Re-inspection required | Wall sign is set to run all night, needs to turn off at midnight per Tucson's outdoor lighting code. Verification of photocell, or other means, that dims the LED board to 200 nits or less after sunset is needed. LED board is switching images every 8 seconds, Tucson requires 60 seconds minimum between image changes. |
|
| 08/04/2026 | COT - ENGR - Sign Electrical | Passed | Timers, photocells, and intervals have been corrected. All signs are installed in accordance with approved plans. |