Inspection Status: Not Ready
Inspection History: COT - ENGR - Sign Footing and Excavation
| Date |
Description |
Inspector |
Results |
Comments |
| 07/12/2024 |
COT - ENGR - Sign Footing and Excavation |
|
Not Ready |
insufficient clearance from reinforcing steel to earth, and wrong vertical reinforcing. #5 verts installed instead of #7. reinforcing to be welded should be A706, not A615. |
| 07/18/2024 |
COT - ENGR - Sign Footing and Excavation |
|
Passed |
I spoke to Josh Garcia on the phone and he informed me that he instructed the contractor to put number seven bar in between the number five bars and the rings are supposed to be number three bars |