| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2026 | COT - ENGR - Signage Final | Not Ready | Waiting on Sign Electrical inspection to be complete. | |
| 10/05/2026 | COT - ENGR - Signage Final | Not Ready | -For Signage Electrical Inspection- Sign company will need to provide pictures of power disconnects at j box behind signs A through D inside wall per plan. Shut off switches are not visible on these signs. Existing sign cabinets E,G,H have shut off switches on signs. Clearly labled circuit for signs is in place in electric panel. Next to panel is a timer but it is not set to comply with Tucson outdoor lighting code. -For Signage Final inspection- There are UL stickers and manufacturer stickers on exterior of new signs, however Signage Electrical Final needs to pass prior to Signage Final Inspection. |