Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - ENGR - Sign Electrical
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/30/2026 | COT - ENGR - Sign Electrical | Not Ready | Permit calls for Dedicated circuit that is clearly labeled for signs. A timer exists but it it missing the on and off set screw settings and is currently manually operated. A programmed timer set to comply with Tucson Outdoor Lighting Code is required. Power Disconnect is visible only on Illuminated sign B, not on the other two illuminated signs installed. |
|
| 05/12/2026 | COT - ENGR - Sign Electrical | Passed | Circuit for signs labeled in breaker panel and timer set correctly. Disconnect switches are on signs or directly behind them on parapet. |