Inspection Status: Not Ready

Inspection History: COT - ENGR - Sign Electrical

Date Description Inspector Results Comments
04/30/2026 COT - ENGR - Sign Electrical Not Ready Permit calls for Dedicated circuit that is clearly labeled for signs. A timer exists but it it missing the on and off set screw settings and is currently manually operated. A programmed timer set to comply with Tucson Outdoor Lighting Code is required.
Power Disconnect is visible only on Illuminated sign B, not on the other two illuminated signs installed.
05/12/2026 COT - ENGR - Sign Electrical Passed Circuit for signs labeled in breaker panel and timer set correctly. Disconnect switches are on signs or directly behind them on parapet.