07/14/2025 TRSP - ROW - Pre-Activity Field/Pre-Construction Meeting Passed Good Morning,

My name is Andrew Quinn, I am a Fire Inspector with Tucson Fire. I was told you had a question about the proximity of your mailbox to a fire hydrant. Per the International Fire Code, which Mayor and Council adopted as the Tucson Fire Code, "unobstructed access to fire hydrants shall be maintained at all times. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants (507.5.4). A 3 foot clear space shall be maintained around the circumference of fire hydrants, except as otherwise required or approved (507.5.5)." Also state statute 28-873 #5 a person shall not stop, stand or park a vehicle within 15 feet of hydrant. I hope this information answers your questions. Feel free to contact me if you have further questions. Have a good day.

Regards,


Andrew Quinn
Fire Code Inspector
Tucson Fire Department