Inspection Status: Re-inspection required
Inspection History: TRSP - ROW - Concrete - Subgrade/Forms (Pre-Pour)
| Date |
Description |
Inspector |
Results |
Comments |
| 11/05/2026 |
TRSP - ROW - Concrete - Subgrade/Forms (Pre-Pour) |
|
Re-inspection required |
The site is overly saturated with water with visible footprints in the mud, needs to be re-compacted, no expansion material on site, and no difference in depth between sidewalk and driveway. Sidewalk should be a minimum of 4 inches thick and driveway shall be a minimum of 6 inches thick. |
| 11/06/2026 |
TRSP - ROW - Concrete - Subgrade/Forms (Pre-Pour) |
|
Passed |
Site is ready for concrete |