Parcel: 141460590


Addresses:

9659 E HARKES DR


Inspection Status: Re-inspection required

Inspection History: TRSP - ROW - Concrete - Subgrade/Forms (Pre-Pour)

Permit Number - TR-ANN-1024-00608

Inspection Description - TRSP - ROW - Concrete - Subgrade/Forms (Pre-Pour)

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
01/13/2025 TRSP - ROW - Concrete - Subgrade/Forms (Pre-Pour) Re-inspection required please fix expansion joints for driveway apron to 6 inches, please fix subgrades unevenness and foreign material
01/15/2025 TRSP - ROW - Concrete - Subgrade/Forms (Pre-Pour) Re-inspection required Driveway still needs 6 inch expansion joint, subgrade material to loose, re-compaction required
01/17/2025 TRSP - ROW - Concrete - Subgrade/Forms (Pre-Pour) Not Ready corrections have not been implemented. Please re-compact subgrade and install 6 inch expansion joints to driveway apron.
01/22/2025 TRSP - ROW - Concrete - Subgrade/Forms (Pre-Pour) Passed Subgrade compacted, 6 inch expansion joint on site, will need to be installed for driveway apron, approved