Inspection Status: Re-inspection required
Inspection History: TRSP - ROW - Concrete - Acceptance (Post-Pour)
| Date |
Description |
Inspector |
Results |
Comments |
| 05/13/2026 |
TRSP - ROW - Concrete - Acceptance (Post-Pour)
|
|
Re-inspection required |
two sidewalk panels east of driveway are out of spec and will need replacement, marked with pink paint. All other panels and expansion joints checked, and verified |
| 05/22/2026 |
TRSP - ROW - Concrete - Acceptance (Post-Pour)
|
|
Passed |
two out of spec sidewalk panels have been replaced, expansion joints added where new concrete meets existing. Verified with level that panels are within grade spec, approved. |