Inspection Status: Partial Pass
Inspection History: COT - FCON - Alarm - Final
| Date |
Description |
Inspector |
Results |
Comments |
| 06/21/2024 |
COT - FCON - Alarm - Final |
|
Partial Pass |
Comm. failure not reporting, rest of alarm tested. |
| 07/03/2024 |
COT - FCON - Alarm - Final |
|
Passed |
|
| 04/26/2024 |
COT - FCON - Alarm - Final |
|
Re-inspection required (with fee) |
As built plans shall reflect actual sequence of operations. Activation of hood shall send a general fire alarm (not supervisory). Dedicated alarm circuit shall be located an locked out. Batteries shall be labeled. Wires from tamper switch shall be protected in conduit. |
| 10/19/2023 |
COT - FCON - Alarm - Final |
|
Re-inspection required (with fee) |
No plan set on site. |