Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.
Inspection Status: Partial Pass
Inspection History: COT - FCON - Alarm - Final
| Date |
Description |
Inspector |
Results |
Comments |
| 06/21/2024 |
COT - FCON - Alarm - Final |
|
Partial Pass |
Comm. failure not reporting, rest of alarm tested. |
| 07/03/2024 |
COT - FCON - Alarm - Final |
|
Passed |
|
| 04/26/2024 |
COT - FCON - Alarm - Final |
|
Re-inspection required (with fee) |
As built plans shall reflect actual sequence of operations. Activation of hood shall send a general fire alarm (not supervisory). Dedicated alarm circuit shall be located an locked out. Batteries shall be labeled. Wires from tamper switch shall be protected in conduit. |
| 10/19/2023 |
COT - FCON - Alarm - Final |
|
Re-inspection required (with fee) |
No plan set on site. |