Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - FCON - Alarm - Final
Permit Number - TF-FCP-1122-00024
Inspection Description - COT - FCON - Alarm - Final
Inspection Status - Partial Pass
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/21/2024 | COT - FCON - Alarm - Final | Partial Pass | Comm. failure not reporting, rest of alarm tested. | |
07/03/2024 | COT - FCON - Alarm - Final | Passed | ||
04/26/2024 | COT - FCON - Alarm - Final | Re-inspection required (with fee) | As built plans shall reflect actual sequence of operations. Activation of hood shall send a general fire alarm (not supervisory). Dedicated alarm circuit shall be located an locked out. Batteries shall be labeled. Wires from tamper switch shall be protected in conduit. | |
10/19/2023 | COT - FCON - Alarm - Final | Re-inspection required (with fee) | No plan set on site. |