Inspection Status: Partial Pass

Inspection History: COT - FCON - Alarm - Final

Date Description Inspector Results Comments
06/21/2024 COT - FCON - Alarm - Final Partial Pass Comm. failure not reporting, rest of alarm tested.
07/03/2024 COT - FCON - Alarm - Final Passed
04/26/2024 COT - FCON - Alarm - Final Re-inspection required (with fee) As built plans shall reflect actual sequence of operations. Activation of hood shall send a general fire alarm (not supervisory). Dedicated alarm circuit shall be located an locked out. Batteries shall be labeled. Wires from tamper switch shall be protected in conduit.
10/19/2023 COT - FCON - Alarm - Final Re-inspection required (with fee) No plan set on site.