Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: TF-FCP-0625-00476

Parcel: 12218229B


Addresses:

1138 N RICHEY BL

Inspection Status: Re-inspection required

Inspection History: FCON – OH Piping & Hydro

Date Description Inspector Results Comments
06/27/2025 FCON – OH Piping & Hydro Re-inspection required 1st floor north unit has a leaker. System lost 10 psi during the test. TFD was not able to see the overhead piping in the ground floor units due to the piping was covered by spray in insulation. Contractor shall provide the Contractor’s Material and Test Certificate for Aboveground Piping.