Inspection Status: Re-inspection required
Inspection History: FCON – OH Piping & Hydro
| Date |
Description |
Inspector |
Results |
Comments |
| 06/27/2025 |
FCON – OH Piping & Hydro |
|
Re-inspection required |
1st floor north unit has a leaker. System lost 10 psi during the test. TFD was not able to see the overhead piping in the ground floor units due to the piping was covered by spray in insulation. Contractor shall provide the Contractor’s Material and Test Certificate for Aboveground Piping. |