Inspection Status: Re-inspection required (with fee)

Inspection History: COT - FCON - Hood System - Final

Date Description Inspector Results Comments
06/09/2023 COT - FCON - Hood System - Final Re-inspection required (with fee) Exhaust did not activate with actuation of system. System not tied into alarm.
06/16/2023 COT - FCON - Hood System - Final Passed