Permit: TF-FCP-0425-00323

Parcel: 10123516B


Addresses:

3742 W RIVER RD

Inspection Status: Partial Pass

Inspection History: COT - FCON - Alarm - Final

Date Description Inspector Results Comments
10/06/2025 COT - FCON - Alarm - Final Partial Pass Tested the following items:
-Water Flow, Tamper Switch, Pull Station, FACP Smoke, Kitchen Hood Switch. All ok.
-RTU 3, 4, 6, 9, 10, 12 all passed.
Need to address the following items:
-Remove strobe in FACP room.
-Verify RTU 1, 2, 5, 8, and 11. No signal to panel on shutdown or no power.
10/14/2025 COT - FCON - Alarm - Final Passed