Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - FCON - Alarm - Final
Permit Number - TF-FCP-0425-00323
Inspection Description - COT - FCON - Alarm - Final
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2025 | COT - FCON - Alarm - Final | Partial Pass | Tested the following items: -Water Flow, Tamper Switch, Pull Station, FACP Smoke, Kitchen Hood Switch. All ok. -RTU 3, 4, 6, 9, 10, 12 all passed. Need to address the following items: -Remove strobe in FACP room. -Verify RTU 1, 2, 5, 8, and 11. No signal to panel on shutdown or no power. |
|
| 10/14/2025 | COT - FCON - Alarm - Final | Passed |