Inspection History: COT - FCON - Alarm - Final

Permit Number - TF-FCP-0223-00378

Inspection Description - COT - FCON - Alarm - Final

Inspection Status - Not Ready

Date Description Inspector Results Comments
COT - FCON - Alarm - Final Not Ready
10/04/2023 COT - FCON - Alarm - Final Partial Pass Need monitoring permit. All alarm and booster batteries need to be labled with in service dates. Stairwell signs will match smoke detector addresses. Elevator door mag locks shall be tested. All devices on 2, 3 and 4 worked except SD in 405. Floor 1 devices shall be tested. Need ROC and 1st year inspection report.
10/18/2023 COT - FCON - Alarm - Final Partial Pass Ground fault shall report to panel. Device addresses shall be available at central station.
10/19/2023 COT - FCON - Alarm - Final Passed