Inspection Status: Not Ready
Inspection History: COT - FCON - Alarm - Final
| Date |
Description |
Inspector |
Results |
Comments |
|
COT - FCON - Alarm - Final |
|
Not Ready |
|
| 10/04/2023 |
COT - FCON - Alarm - Final |
|
Partial Pass |
Need monitoring permit. All alarm and booster batteries need to be labled with in service dates. Stairwell signs will match smoke detector addresses. Elevator door mag locks shall be tested. All devices on 2, 3 and 4 worked except SD in 405. Floor 1 devices shall be tested. Need ROC and 1st year inspection report. |
| 10/18/2023 |
COT - FCON - Alarm - Final |
|
Partial Pass |
Ground fault shall report to panel. Device addresses shall be available at central station. |
| 10/19/2023 |
COT - FCON - Alarm - Final |
|
Passed |
|