Inspection Status: Partial Pass
Inspection History: COT - FCON - Alarm - Final
Permit Number - TF-FCP-0125-00085
Inspection Description - COT - FCON - Alarm - Final
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2026 | COT - FCON - Alarm - Final | Partial Pass | Tested only fire pump and first floor only, Still need fire pump phase reversal and descriptions for 1st floor community rooms, laundry rooms need smoke detection and water heater rooms need CO detection. | |
| 03/11/2026 | COT - FCON - Alarm - Final | Partial Pass | Tested floors 2 & 3, 4th floor tamper not reporting correct, smokes in rooms 411 & 404 sets off whole building, 4th floor booster panel not reporting, trash room heat not reporting correct. |