Inspection Status: Partial Pass
Inspection History
Permit Number - TD-DEV-1222-00060
Inspection Description -
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/03/2025 | Partial Pass | 9/3/25 Retaining wall. Footer to plan and is is ok to pour. Reinforcing correct. Dimensions correct. Schedule next inspection for wall when forms, reinforcing and weeps are ready. |
||
| 09/08/2025 | Not Ready | Rebar and the forms are not complete. Also there is cross section A on DP page 14 that shows a curb above grade. Curb is not shown in other details. Architect needs to clarify. | ||
| 09/10/2025 | Partial Pass | 9/10/25 -Retaining wall to North of drive through. Rebar is correct to plan. Forms, weeps, snap ties all correct. #4 bar at top correct for railing. Okay to pour Wall. Patch snap tie holes. Do not backfill until we see it after forms stripped. We need to see the underdrain, gravel pocket. -2 Screen wall footers at corners of outside seating area are correct. Okay to pour these footers. |