Inspection History Details
Inspection Status: Partial Pass
Inspection History: For trash and recycling enclosures
Permit Number - TD-DEV-1123-00451
Inspection Description - For trash and recycling enclosures
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/16/2025 | For trash and recycling enclosures | Partial Pass | Side wall verts need to be moved out 8”+ in order for gate openings to clear 12’-8” ID minimum. Andy will send picture of correct dimension. Dimension will be verified in order to move forward and pour footer. |
|
| 04/22/2025 | For trash and recycling enclosures | Partial Pass | Wall verts on enclosure are 27’-4” and correct. Footer can be poured. I also inspected 7 light poles. These are per plan with electrical conduit 18”+ below grade. Light poles are ready to be poured. |
|
| 05/27/2025 | For trash and recycling enclosures | Partial Pass | Grout insepection | |
| 06/09/2025 | For trash and recycling enclosures | Partial Pass | Okay to pour floor. |