Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Inspection Status: Re-inspection required

Inspection History: ENGR Engineering Final

Permit Number - TD-DEV-1122-00049

Inspection Description - ENGR Engineering Final

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
11/08/2024 ENGR Engineering Final Re-inspection required Move the van accessible sign to the left post
Either remove and fix ramp that measured at 7.4% or add rails to both sides
Water harvesting islands grade needs to be 6 to 9" below asphalt at saw cut
Add one water harvesting cut next to the right side of dumpster enclosure
West side move fence to building
East side move fence to rear of trash enclosure