Inspection Status: Not Ready
Inspection History: Grading Progress ENGR
Permit Number - TD-DEV-1122-00029
Inspection Description - Grading Progress ENGR
Inspection Status - Not Ready
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/07/2026 | Grading Progress ENGR | Not Ready | contractor needs regrade the drive-through area before placing AB. | |
| 02/06/2026 | Grading Progress ENGR | Not Ready | 2/6/26 Subgrade is good with exception of the Handicap parking area. Hubs are sufficient and drainage is correct, slopes correct and compaction testing is sufficient and complies. The Basin behind the Refuse Enclosure is a little too deep, I discussed this with the contractor. The handicap parking area slope is defined by vertical curb on either side. One side is close to 2% and on the other side the curbs exceeds it. I recommend this curb over 2% be replaced. The Subgrade between the curbs averages out to a slope over 2%. Fix this problem and reschedule Grading progress when ready. |
|
| 02/09/2026 | Grading Progress ENGR | Passed | ||
| 12/22/2025 | Grading Progress ENGR | Not Ready | contractor is not ready to check the grade subgrade needs to have surveyor come in and shoot in all the hubs. No subcontractor on site just the superintendent . |