Inspection History Details
Inspection Status: Re-inspection required
Inspection History: ENGR Grading Final
Permit Number - TD-DEV-1122-00029
Inspection Description - ENGR Grading Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2026 | ENGR Grading Final | Re-inspection required | 2/13/26 AB has been placed and density complies but Handicap Parking is still over 2%. Curbs may need to rebuilt and Asphalt cut may need to be expanded away from handicap parking to comply. Drainage may bypass current curb cut with this condition. This needs redesigned so slope and drainage will work without puddling. |
|