Permit: TD-DEV-0825-00216

Parcel: 105102440


Addresses:

495 E WETMORE RD

Inspection Status: Partial Pass

Inspection History: For trash and recycling enclosures

Date Description Inspector Results Comments
05/14/2026 For trash and recycling enclosures Partial Pass Approved building plans show a modified double Refuse Enclosure. Detail C/A 0.1 and the same layout is shown on DP. Detail shows no center block column to Hang Gates. Just two gates hung from side walls instead of 4. Minimum 10' Clear for dumpsters met. Otherwise Footer Dimensions and reinforcing is correct or exceeds TSM standard details figures 3 and 3a in TSM 8-01.9.0...
Contractor sent pictures of 2 Verts at wall ends and 3 in corners. Okay to pour Footer
05/18/2026 For trash and recycling enclosures Partial Pass Wall finished okay to grout wall. Schedule refuse enclosure inspection/s for us to look at the bollards and the rebar mat in floor the day before pour.
05/29/2026 For trash and recycling enclosures Partial Pass 5/29/26
I have not received pictures of the reinforcing 3" clear of the dirt for The Whole mat. Also use full thickness expansion material at walls. Bollard footers good, everything else good. Okay to pour bollards and floor with pictures.