Inspection History Details
Inspection Status: Not Ready
Inspection History
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2026 | Not Ready | -Curb ramp at south end of crosswalk south of the building, leading to ROW sidewalk does not comply. Ramp and landings on both sides of it exceed 2.0% cross slope. -No overflow outlet curb cut at NW basin as shown on plan. -Curb ramp on west side of crosswalk west of building complies but one side has large gap between curb and ramp that needs to be repaired. |