Inspection Status: Partial Pass

Inspection History

Permit Number - TD-DEV-0723-00325

Inspection Description -

Inspection Status - Partial Pass

Date Description Inspector Results Comments
08/21/2025 Partial Pass 08/21/25, sidewalks on the south front side of building are good to pour. Bollards will be required on the front entry circle drive. See Tucson standards as described on your plan set.
09/03/2025 Partial Pass Good to pour.
09/04/2025 Failed 09/04/25, Do not pour the stairs and ramp in the garden area that is considered a therapy ramp. Slope is exceedingly more than the required 8.333% allowed by code. Unless the architect/engineer can prove by medical means that this pitch of 14.5% is required do not pour.
10/06/2025 Partial Pass Contractors good to pour the ramp for the hospital in the front. Contractor needs to remove part of the curb in the sidewalk on the southwest corner where the valley gutters are at. Contract is good to pour for that valley gutter on the south west quadrant.