Inspection Status: Passed
Inspection History: Consultation SITE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/22/2026 |
Consultation SITE |
|
Passed |
Depths of water harvesting areas are good, okay for planting. |
| 05/29/2026 |
Consultation SITE |
|
Passed |
Site visit to discuss water flow issues: Areas of concentrated water flow listed below require erosion control measures, the marked up plan of page C201 proposing riprap splash pads is an acceptable solution. Areas of concern are: 2 culvert outlets on south side, SW parking lot transition to basin P1, basin P1 outflow pipe, downspout scupper on west side, 2 additional downspouts on west side, basin P2 outflow pipe, 2 curb cuts on east side PAAL, 2 ends of retaining wall where flow will concentrate. |
| 06/02/2026 |
Consultation SITE |
|
Passed |
Detention Area P2 outlet structure: okay to core holes below grate invert at 9" depth to achieve proper retention height, same as was done in Area P1. |
| 10/16/2025 |
Consultation SITE |
|
Partial Pass |
Site consultation to review SWPPP updates. Book has been replaced due to previous water damage, Porta-potty spill has been remediated, porta-potties are staked down now. Wattle has been refreshed throughout site. *One area of issue behind trailer: wattle isn't in contact with the ground, rills need to be filled in. Requested that ADEQ sign be moved closer to public view. |
| 10/22/2025 |
Consultation SITE |
|
Partial Pass |
Doctor called in for consultation on the RCP pipe that’s at the entryway of the project installed 77 lineal feet of RCP pipe good to backfill |
| 12/17/2025 |
Consultation SITE |
|
Partial Pass |
In order to use adjacent property for employee parking, a Temporary Use Permit will be required. |