Inspection History Details
Inspection Status: Partial Pass
Inspection History: For trash and recycling enclosures
Permit Number - TD-DEV-0523-00250
Inspection Description - For trash and recycling enclosures
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/02/2025 | For trash and recycling enclosures | Partial Pass | Trash enclosure (both) footing excavation has correct reinforcement and dimensions, okay to pour. | |
| 09/16/2025 | For trash and recycling enclosures | Partial Pass | 9/16/25 Slabs okay to pour. Slope is correct. Compaction test done. Reinforcing correct. Correct to survey. 9/16/25 Horizontal reinforcing needed 16” oc in wall. Put it in and build the wall up another 2 courses before pre grout inspection on 1st lift. |
|
| 09/25/2025 | For trash and recycling enclosures | Partial Pass | 9/25/25 Ok to grout walls. Call us back out for pregrout inspection when done w with second lift. Grout all cells Vibrate all grout. |
|
| 10/10/2025 | For trash and recycling enclosures | Partial Pass | 10/10/25 Bond beam at top of wall correct for both enclosures. Okay to grout second lift-vibrate all grout. |