Permit: TD-DEV-0325-00077

Parcel: 141186590


Addresses:

10080 E OLD VAIL RD

Inspection Status: Not Ready

Inspection History: ENGR Paving

Date Description Inspector Results Comments
02/26/2026 ENGR Paving Not Ready 2/26/26
Site is paved. No previous paving inspections. I see several areas that have potential issues with puddling. I showed contractor areas of concern. A flood test to see how the pavement drains should be done.

I also saw that the landscaped areas should be depressed 6” where possible. I showed the Contractor the detail in the DP and he understands.
02/27/2026 ENGR Paving Not Ready After performing a flood test it was observed that two (2) areas on the East side of the building had pooling water in excess of 0.5 inches due to surface conditions of the asphalt. One recommendation as a means of remediation would be to depress the landscape areas (as required per plans, page 14, detail G) immediately adjacent to the pooling and install curb cuts to relieve the excess water into the landscape areas.
04/08/2026 ENGR Paving Passed Drainage cutouts have been added to relieve surface puddles. Paving is complete in accordance with approved plans.