Inspection History Details
Inspection Status: Partial Pass
Inspection History
Permit Number - TD-DEV-0324-00096
Inspection Description -
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/09/2025 | Partial Pass | 12/9/25 30' x 3' sidewalk formed for domes in front of front of entryway, behind line of 7 bollards at 5' oc. Bollard footer dims correct. 4" sidewalk for domes have #4 @ 16" EW. Dowels will be placed on either side of domes for reinforced turn down at bollards and sidewalk to building. Building also has dowels. Ok to pour domes and bollards pending they are plumb and correct before pour. To east of 5' OC bollards the spacing changes to 8' OC per plan this sidewalk also has no grade separation. 7 are dug. 8' spacing is okay per accepted Tsmr. |
||
| 12/10/2025 | Partial Pass | 12/10/25 Sidewalk in front of entry way and further east to turn in adjacent block wall.Forms are good. Dowels in place. Turndowns correct. Reinforcing spacing good. Pictures showing rebar mat being centered in area of sidewalk that needs to traversed with concrete buggy will be sent. Expansion material in place. Place expansion joints at 40' intervals. Okay to pour Sidewalk. |
||
| 12/12/2025 | Partial Pass | 12/12/25 Sidewalk section not Poured yesterday ready between cold joints. Toe down at bollard correct and dowels and expansion joints good. Another formed area in front of cart service door ready with expansion joints material and dowels. Okay to pour these areas. |