Permit: TC-UTL-0524-00018

Parcel: 13613020A

Inspection Status: Passed

Inspection History: COT - LCEL - Electrical Underground 

Date Description Inspector Results Comments
06/01/2026 COT - LCEL - Electrical Underground  Passed 06/01/2026
(2) 6" & (4) 4" sch 40 conduit trenched from transfer to SES run of 61'. Okay to backfill and pull feeder wires. (3) 3/4" sch 40 conduit at light posts with CU grounding, verified reinforcement per plan.