Inspection Status: Re-inspection required

Inspection History: BULD - Electrical Clearance

Permit Number - TC-SOL-0925-01219

Inspection Description - BULD - Electrical Clearance

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
12/05/2025 BULD - Electrical Clearance Re-inspection required 12/05/2025
Unable to verify AWG wires size on photos - please upload closeup of wire sizes. SolarApp checklist calls for 21 modules on the roof, but photos are only showing 20 panels laid out differently to plan layout - please verify count and upload photo of all panels or update plans to reflect change in field.
12/10/2025 BULD - Electrical Clearance Passed 12/10/2025
Clearance to TEP DGC. Approved per uploaded plans and SolarAPP checklist on 12/04/2025 showing 20 modules on rooftop, verified wire sizes with uploaded photos.
12/12/2025 BULD - Electrical Clearance Passed 12/10/2025
Clearance to TEP DGC. Approved again per uploaded plans and SolarAPP checklist showing 20 modules on rooftop, verified wire sizes with uploaded photos. Reviewer has also approved planset.