Inspection History Details
Inspection Status: Canceled
Inspection History: COT - RSOL - Electrical Final Solar Project
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/27/2024 | COT - RSOL - Electrical Final Solar Project | Canceled | CANCELED BY INSPECTOR Homeowner said RDX electrician made changes in the main electric panel last week. These changes have caused the microwave and clothes dryer to immediately trip. Have a licensed electrician trouble shoot the wiring and breaker sizes and correct as needed. Owner indicated that the dryer is now on a 20 amp circuit, etc..... The solar and the house panel will not be inspected until corrections are complete. Be prepared to mount the roof for a detailed inspection of the panel attachments and grounding, as well as all wall mounted panel's wiring. If inspection fails again, there will be a re-fee. |
|
| 11/19/2024 | COT - RSOL - Electrical Final Solar Project | Not Ready | ||
| 11/20/2024 | COT - RSOL - Electrical Final Solar Project | Passed |