Inspection Status: Re-inspection required

Inspection History: BULD - Electrical Clearance

Date Description Inspector Results Comments
09/24/2026 BULD - Electrical Clearance Re-inspection required 9-24-26 service outlet required at main panel* feeders out of weatherhead shall be a minimum of 2 feet.* properly bond water* gas bond must be continuous to panel not able to put two number four bears under the same acorn at ground rod, must go completely passed all the way to panel and terminate to ground lugs.
09/28/2026 BULD - Electrical Clearance Passed