Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: TC-RES-1225-05917

Parcel: 138230420


Addresses:

650 W CALLE RITA

Inspection Status: Passed

Inspection History: COT - RSPL - Yard Water LineĀ 

Date Description Inspector Results Comments
02/03/2026 COT - RSPL - Yard Water LineĀ  Passed 02/03/2026
PEX line in 2' trench with blue tracer from meter to riser at house holding under test at 82psi. Verified contractor will add pressure reduction valve if water utility does not reduce below 80psi. Okay to backfill with shading materials.