Inspection Status: Re-inspection required
Inspection History: COT - RSEL - Electrical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/23/2025 | COT - RSEL - Electrical Final | Re-inspection required | 7.23.25 Missing gfci under kitchen sink. Missing hammer arrester at main kitchen. Missing hammer arrester at laundry. Missing outlet at primary bedroom Toilet center must be 15" from lav and bath 3rd party verify non ul listed mini s-lots Paint exterior plastic Ground water heater Insulate water lines at water heater Arc faults missing at panel Panel not per plan |
|
| 07/30/2025 | COT - RSEL - Electrical Final | Not Ready | 7-30-25: not ready-contractor will reschedule. | |
| 08/18/2025 | COT - RSEL - Electrical Final | Passed | 8.18.25 Satisfactory corrections implemented as requested APPROVED |