Inspection Status: Re-inspection required

Inspection History: RSBU - Building Final 

Permit Number - TC-RES-1224-07482

Inspection Description - RSBU - Building Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
10/17/2025 RSBU - Building Final  Re-inspection required 1. In the container; light switch electrical needs grommet; incoming Romex for panel needs grommet.

2. Exposed romex needs to be in conduit inside the container

3. Separate the grounds and neutrals in sub panel.

4. Provide receptacles for lighting in container or hardwire.

5. Cannot run romex on the exterior, please use THWN wires in the conduit.

6. Use liquid tite conductor and fittings on all fixture connections exterior.
10/28/2025 RSBU - Building Final  Passed