Inspection History Details
Inspection Status: Re-inspection required
Inspection History: RSBU - Building Final
Permit Number - TC-RES-1224-07451
Inspection Description - RSBU - Building Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/21/2025 | RSBU - Building Final | Re-inspection required | Not ready. Add arc fault breakers per note 9 on electrical notes. Provide gfci receptacles at counter tops. Receptacle exceeding 2' from range. Add nail plates to electrical lines that are less than an 1 1/4". Add ground screws to all metal boxes. Cover up holes before final inspection. 4/21/2025 | |
| 05/06/2025 | RSBU - Building Final | Passed | 5-6-25, required corrections from previous inspection were made. Building final approved. |