Inspection Status: Re-inspection required

Inspection History: COT - RSEL - Electrical FinalĀ 

Date Description Inspector Results Comments
05/28/2026 COT - RSEL - Electrical FinalĀ  Re-inspection required 5-28-26: have draftsman submit a letter to the city documenting that 1/2" drywall will be installed at the back porch ceiling. Please include type of drywall screw and screw spacing. Reschedule an inspection prior to tape/texture, install a weather resistant GFCI receptacle at exterior wall and add clamps to secure rigid conduit at 4' intervals.
Note: all wood framing must be sealed or painted.