Inspection Status: Re-inspection required
Inspection History: COT - RSEL - Electrical Final
Permit Number - TC-RES-1224-07262
Inspection Description - COT - RSEL - Electrical Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/18/2025 | COT - RSEL - Electrical Final | Re-inspection required | 2-18-25, box in romex , missing gfci's in kitchen, install, arch fault where required by code, correct bathroom wiring, install smoke detectors in each bedroom and in hallway, and add missing receptacle covers to receptacles. | |
| 02/21/2025 | COT - RSEL - Electrical Final | Passed | 2/21/25: GFCI Outlets are installed in kitchen, AFCI Breaker installed in panel for bedrooms, bathroom wiring is corrected, missing receptacles covers are installed, and smoke detectors are installed in each bedroom and CO2/Smoke detector in hallway. Okay to close out this permit. |