Inspection History Details
Inspection Status: Not Ready
Inspection History: RSBU - Building Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/11/2024 | RSBU - Building Final | Not Ready | 3/11/24: not ready | |
| 06/26/2024 | RSBU - Building Final | Not Ready | ||
| 07/02/2024 | RSBU - Building Final | Re-inspection required | 3/11/24: not ready 7/2/24: no access to panel, multiple circuits off, secure gas line at back porch, water hammer arrestor missing at dishwasher, water heater missing fuses, no ladder for roof access. STOPPED INSPECTION NOT READY PLEASE UNLOCK MAIN PANEL. |
|
| 07/03/2024 | RSBU - Building Final | Re-inspection required | 3/11/24: not ready 7/2/24: no access to panel, multiple circuits off, secure gas line at back porch, water hammer arrestor missing at dishwasher, water heater missing fuses, no ladder for roof access. STOPPED INSPECTION NOT READY PLEASE UNLOCK MAIN PANEL. 7/3/24: exterior receptacles not GFCI, insulate and seal hose bib at front of house, panel schedule incomplete, 2 circuits required at kitchen, insulate hose bib at back porch, A/C drain must terminate 6" above grade, exterior plastic piping must be UV coated, T&P must terminate 6" above grade, water hammer arrestor missing at refrigerant, dryer vent exhaust must have screen removed from T-top, smoke detector missing outside bedroom, SWG METER needs clearance of 3' from all openings, storage unit at backyard not on site plan. |
|
| 07/10/2024 | RSBU - Building Final | Re-inspection required | 7/10/24: Gas meter needs to be relocated to comply with clearance issues. | |
| 07/11/2024 | RSBU - Building Final | Not Ready | ||
| 08/20/2024 | RSBU - Building Final | Passed |