Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSPL - Plumbing Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/17/2025 | COT - RSPL - Plumbing Final | Re-inspection required | 17 Mar 25 1. Exterior outlets need to WR rated, to include the hvac service outlet on rooftop. 2. Need metal collar on water heater ceiling penetration 3. Water heater t/p discharge needs to terminate no more than 6 inches from the ground. 4. Dryer exhaust needs to have backdraft damper, remove screen. 5. Laundry is not on GFCI circuit. 6. Range needs anti-tip bracket. 7. Hose bibs needs to be anti-siphon. |
|
| 03/24/2025 | COT - RSPL - Plumbing Final | Passed |