Inspection Status: Re-inspection required
Inspection History: COT - RSME - Mechanical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 10/31/2025 |
COT - RSME - Mechanical Final |
|
Re-inspection required |
10-31-25: paint all exterior pvs/abs on rooftop, missing mini-split head ( a revision with calculations from architect/engineer is required if you choose to only use one). The mini split is over amped-max breaker is a 15 amp, properly anchor mini split to pad, replace 80 amp main house breaker from main electrical panel to Casita with a 100amp, and wrap hot copper lead of water heater together with pressure relief valve with R-3 insulation. |
| 11/25/2025 |
COT - RSME - Mechanical Final |
|
Passed |
|