Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior Clips/Sheathing 

Permit Number - TC-RES-1222-01381

Inspection Description - COT - RSBU - Exterior Clips/Sheathing 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
01/08/2024 COT - RSBU - Exterior Clips/Sheathing  Re-inspection required 1/8/23: anchor bolts must be installed 32"O.C missing throughout, 2x12 roof joist were substituted with 2x6. Engineer must review and resubmit changes, exterior porch at Arizona room is going to be omitted. Must be shown on plans. Door opening and height not per plan Revision is required. Continue at risk, revision will be needed at final. door height does not meet IRC requirements.
01/16/2024 COT - RSBU - Exterior Clips/Sheathing  Passed