Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 06/20/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
6/20/23: Wall Brace schedule missing Anchor bolts ( 32" O.C) and Anchor bolt missing 12" from end of sill plate. Sheathing schedule needs to be followed throughout wall brace schedule. (WB-1: 1/2" PLY SHEATHING WITH 8d NAILS AT 6" O.C. AT EDGES AND 12" OC. AT FIELD. BLOCK ALL PLYWOOD EDGES. SILL PLATE ATTACHED WITH 1/2" ANCHOR BOLT @ 32" O.C. MAX. ALL EXTERIOR IS IN SHEAR). Plans need to be revised (state no work to be done on north side of house) but new joist were installed throughout the entire house. |
| 08/09/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|