| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/05/2026 | COT - RSPL - Rough Soil | Partial Pass | Revision Required (6/5/2026): Changes were made to the rough soil plumbing that are not reflected on the approved plans. The existing DWV serving the south bathroom was replaced and must be shown on the revised drawings. A laundry sink was added in the laundry room and is required to be included in the revision. The north bathroom plumbing layout must also be revised to accurately reflect the installed fixture arrangement. The pressure test passed. Backfill is approved at risk, contingent upon approval of the required plan revisions. |