Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/19/2026 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Partial Pass | need gas pressure test | |
| 05/07/2026 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Re-inspection required | 5/7/26: receptacles required at kitchen counter top, box fill at kitchen (range area) exceeding max box fill 34 cu. In., smoke detectors missing per approved plans @ living room and dining area, circuits tied into sub-panel (should be ran from main panel per approved plans, island has NM cable running underground (UF cable required), hot and neutrals reversed at multiple receptacles, kitchen circuits shall be AFCI and GFCI 20Amp.please recall inspection. | |
| 05/27/2026 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed | 5/27/26 Required CO/smoke detectors will be checked at finals |