Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSEL - Electrical Final
Permit Number - TC-RES-1124-06940
Inspection Description - COT - RSEL - Electrical Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2025 | COT - RSEL - Electrical Final | Re-inspection required | 7/2/25: water hammer arrestor required at dishwasher, Arc-fault breakers missing throughout, exterior plastic piping must be coated for UV protection, main water line must be insulated and wrapped for UV protection, seal knock-out at disconnect at A/C disconnect, sun shield required at flex duct connector, thermostat shall be no higher than 48" AFF, receptacle spacing at kitchen counter not code complaint. | |
| 07/08/2025 | COT - RSEL - Electrical Final | Passed |