Inspection Status: Re-inspection required
Inspection History: COT - RSEL - Electrical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 07/02/2025 |
COT - RSEL - Electrical Final |
|
Re-inspection required |
7/2/25: water hammer arrestor required at dishwasher, Arc-fault breakers missing throughout, exterior plastic piping must be coated for UV protection, main water line must be insulated and wrapped for UV protection, seal knock-out at disconnect at A/C disconnect, sun shield required at flex duct connector, thermostat shall be no higher than 48" AFF, receptacle spacing at kitchen counter not code complaint. |
| 07/08/2025 |
COT - RSEL - Electrical Final |
|
Passed |
|