Parcel: 124031810

Inspection Status: Re-inspection required

Inspection History: RSBU - Building Final 

Permit Number - TC-RES-1124-06940

Inspection Description - RSBU - Building Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
07/02/2025 RSBU - Building Final  Re-inspection required 7/2/25: water hammer arrestor required at dishwasher, Arc-fault breakers missing throughout, exterior plastic piping must be coated for UV protection, main water line must be insulated and wrapped for UV protection, seal knock-out at disconnect at A/C disconnect, sun shield required at flex duct connector, thermostat shall be no higher than 48" AFF, receptacle spacing at kitchen counter not code complaint.
07/08/2025 RSBU - Building Final  Passed 7/8/25
Pass