Inspection History: COT - RSME - Mechanical Final 

Permit Number - TC-RES-1124-06880

Inspection Description - COT - RSME - Mechanical Final 

Inspection Status - Not Ready

Date Description Inspector Results Comments
01/22/2025 COT - RSME - Mechanical Final  Not Ready no access or ladder
01/29/2025 COT - RSME - Mechanical Final  Re-inspection required No insulation in ductwork on roof, please determine heat strips if installed, blocking required on whip and condensate, roof jacks required on roof penetrations, 30 amp max fuse for basic unit, water heater is 40 amp max, paint/seal all spiral duct after insulation is verified, elbow down on condensate required, thermostat is to high on wall